HOW TO SELECT THE BLOWER MODEL

1. Air volume is general shown in terms of
  1. Standard state (Qs) : At 20 0C, 10332 mmH2O, and RH 65%
  2. Normal state (Qn) : At 0 0C, 10332 mmH2O, and RH 0%
2. Performance table shown the capacity at the standard suction state.

3. Performance table shown the pressure at the static pressure.

4. Volume conversion formula

Q2=

Q1X

P1

P2

x

T2

T1

Q1(m3/min) : Air volume in P1 (mmH2O),T1(0K)
Q2(m3/min) : Air volume in P2 (mmH2O),T1(0K)

5. Pressure conversion formula

For pressure Ps = (

10332+P2

10332+P1

-1 )

x

10332

For vacuum  Ps = (

10332+P1

10332+P2

-1 )

x

10332

P1 suction static pressure
P2 dischargr static pressurre
P3 static pressure in catalog

6. Example

Operating specification 

Air volume : 8 m3/min
Suction static pressure : -700 mmH2O
Discharge static pressure : +2100 mmH2O
Suction temperature : 30 0C
Calculation : Air volume (8 m3 /min) converts to STP state

Q=8 x

10332-700

10332

x

273+20

273+30

= 7.21 m3/min

Static pressure changed to

Ps =(

10332+2100

10332-700

-1 )

x 10332 = 3003 mmH2O

7. When different model are able to achieve the same air volume, select smaller model is able to save equipment cost, but bigger model has advantages of lower speed and lower noist.